Panasonic PAW280MAH2 Instructions d'exploitation Page 50

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 74
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 49
50
Electrical Wiring
5.2 Recommended wire lengths and diameters
Important
The letter coding (A to F) used in the following tables refers to the wiring system
diagrams in the next section.
For information on “(A) Power supply of outdoor unit” refer to the “Installation
Instructions“ for the relevant outdoor unit.
Indoor unit
Type (B) Power supply Time delay fuse or circuit breaker
AHU Kit 2.5 mm
2
(AWG#13) 10 – 16 A
Max. 150 m
Control wiring
(C) Inter-unit control wiring
(between outdoor and indoor units
(D) Remote
control wiring
(E) Control wiring
for group control
1
(F) Inter-outdoor-
unit control wiring
1
0.75 mm
2
(AWG# 18)
Use shielded wiring*
or 2.0 mm
2
(AWG# 14)
Use shielded wiring*
0.75 mm
2
(AWG# 18)
Use shielded wiring*
0.75 mm
2
(AWG# 18)
Use shielded wiring*
0.75 mm
2
(AWG# 18)
Use shielded wiring*
Max. 1,000 m Max. 2,000 m Max. 500 m Max. 200 m (total) Max. 300 m
1 “E” and “F” are relevant for ECOi multi connection systems only.
i
Vue de la page 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 73 74

Commentaires sur ces manuels

Pas de commentaire