Installation
2. Cover the thermistor and pipe with aluminum tape.
3. Cover the aluminum tape with thermal insulation.
4. Fix thermal insulation and wiring with two bands. Then, run the wire downwards in a loop, to
avoid putting tension to it.
For PAW-280MAH2(L) and PAW-560MAH2(L)
1. Upon delivery, for PAW-280MAH2(L) and PAW-560MAH2(L) there is a sensor sleeve sol-
dered to the gas pipe after the expansion valve: Insert the sensor together with some heat
sink paste into the sensor sleeve.
2. Fasten the sensor in an appropriate way (e. g. with a little clip) to prevent it from falling out of
the sleeve.