INSTALLATION INSTRUCTIONS
Single Split System Air Conditioner
This air conditioner uses the refrigerant R410A.
NOTE
External diameter of service port R410A: 5/16"
Remote Controllers
Timer Remote Controller (wired) CZ-RTC2 Timer Remote Controller comes with Instructions Manual.
Wireless Remote Controller
CZ-RWSU1U for U1 and T1 type Indoor units
CZ-RWSC1U for F1 type Indoor units
CZ-RWSK1U for K1 type Indoor units
Units should be installed by licensed contractor according to
local code requirements.
85464369532012
Model No.
Indoor Units
Type Indoor Unit Type 26 36 42 Remarks
U1 4-Way Cassette
S-26PU1U6
(CZ-24KPU1U)**
S-36PU1U6
(CZ-36KPU1U)**
S-42PU1U6
(CZ-36KPU1U)**
with Wired Remote Controller: CZ-RTC2
K1 Wall Mounted S-26PK1U6 with Wireless Remote Controller: CZ-RWSK1U
T1 Ceiling S-26PT1U6 S-36PT1U6 S-42PT1U6 with Wired Remote Controller: CZ-RTC2
F1 Low Silhouette Duct S-26PF1U6 S-36PF1U6 with Wired Remote Controller: CZ-RTC2
** Panel (optional parts)
CV6233186962
Panasonic_PAC-i_IndoorUnit_US-le1 1Panasonic_PAC-i_IndoorUnit_US-le1 1 2011/11/02 15:17:082011/11/02 15:17:08
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONSSingle Split System Air ConditionerThis air conditioner uses the refrigerant R410A.NOTEExternal diameter of service port R41

Page 2 - Please Read Before Starting

10Table 1-6 (Accessories for the Timer Wired Remote Controller)Part Name Figure ‘Q’ty Part Name Figure ‘Q’ty Timer Wired Remote Controller1 Spacers 2

Page 3 - Check of Density Limit

11CAUTION1. This unit requires no additional refrig-erant charge up to 100 ft. tubing length. In case of more than 100 ft., additional refrigerant ch

Page 4 - Vacuum pump

122. SELECTING THE INSTALLATION SITE2-1. Indoor UnitAVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil

Page 5

133. HOW TO INSTALL THE INDOOR UNIT4-Way Cassette Type(U1 Type)3-1. Suspending the Indoor UnitThis unit uses a drain pump. Use a level gauge to check

Page 6 - CONTENTS

143-3. Placing the Unit Inside the Ceiling(1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplie

Page 7 - 1. GENERAL

153-4. Installing the Drain Piping(1) Prepare standard hard PVC pipe for the drain and use the supplied drain hose and hose band to pre-vent water le

Page 8 - Table 1-3 Ceiling

163-5. Checking the DrainageAfter wiring and piping are completed, use the follow-ing procedure to check that the water will drain smooth-ly. For this

Page 9 - Heating preparations

17Ceiling Panel3-6. Before Installing the Ceiling Panel(1) Remove the air-intake grille and air filter from the ceiling panel. (Figs. 3-13 and 3-14)(

Page 10

183-7. Installing the Ceiling Panel(1) Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit.NOTEThe

Page 11

193-9. Duct for Fresh Air There is a duct connection part on side of the indoor unit. (Fig. 3-16)(1) Accessories Check that the following parts are

Page 12 - 4-Way Cassette Type

2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and oper-ating standards. As the installer or service person,

Page 13 - D E B C

20(d) Installing the ceiling panelAttach the ceiling panel to the air-intake plenum. Drawing the panel downwards sets the panel in position temporaril

Page 14 - 8"/ 7

21Wall Mounted Type (K1 Type)3-10. Removing the Wall Fixture from the UnitRemove the set screws and take off the rear panel. (Fig. 3-19)NOTETubing can

Page 15 - Air bleeder

223-12. Installing the Rear Panel on the WallBe sure to confirm that the wall is strong enough to suspend the unit.See either Item a) or b) below depe

Page 16 - 5/16"(4 × 8 mm)

233-13. Removing the Grille to Install the Indoor UnitBasically, these models can be installed and wired without removing the grille. If access to any

Page 17 - Air-intake grille

243-15. Wiring InstructionsGeneral Precautions on Wiring(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carr

Page 18

253-17. Shaping the Tubing(1) Shape the refrigerant tubing so that it can easily go into the hole. (Fig. 3-34)(2) Push the wiring, refrigerant tubin

Page 19 - (S-36PU1U6, S-42PU1U6)

26Ceiling Type (T1 Type)3-19. Suspending the Indoor Unit(1) Place the full-scale diagram (supplied) on the ceiling at the spot where you want to inst

Page 20

27(5) Before suspending the indoor unit, remove the 2 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the

Page 21 - Left-rear tubling

28Ceilingsurface.xorppAhcni 1Suspension boltWasher(supplied)Nut(field supply)Fig. 3-47Fig. 3-48Fig. 3-49(7) Suspend the indoor unit as follows.(a) M

Page 22

293-20. Duct for Fresh AirThere is a duct connection port (knock-out hole) at the right-rear on the panel top of the indoor unit for drawing in fresh

Page 23

3Check of Density LimitThe room in which the air conditioner is to beinstalled requires a design that in the event of refrig-erant gas leaking out, it

Page 24 - Cover plate

30Low Silhouette Ducted Type (F1 Type)3-22. Required Minimum Space for Installation and Service This air conditioner is usually installed above the c

Page 25 - Insulating

313-23. Suspending the Indoor UnitDepending on the ceiling type:• Insert suspension bolts as shown in Fig. 3-58 or• Use existing ceiling supports or c

Page 26 - (field supply)

32 Fig. 3-62 shows an example of installation.3-24. Installing the Drain Piping(1) Prepare standard hard PVC pipe for the drain and use the supplied

Page 27 - Side panel

33CAUTIONDo not install an air bleeder tube as this may cause water to spray from the drain pipe outlet. (Fig. 3-65)If it is necessary to increase the

Page 28 - PVC pipe (field supply)

343-26. Increasing the Fan SpeedIf external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop t

Page 29 - Cut this portion

353-27. When Installing the Indoor UnitConfirm that the indoor unit should be installed in a horizontal position.Use the level gauge or vinyl tube and

Page 30 - 23/72-22

36SUPPLEMENT ON DRAIN PIPINGCheckpoint after installationAfter installation of indoor and outdoor units, panels and electrical wiring, check the follo

Page 31 - Hexagonal nut

374. ELECTRICAL WIRING4-1. General Precautions on Wiring(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carr

Page 32 - Clamps (supplied)

38Inter-unitpower wiringPower wiringInter-unitcontrol wiring8P terminal boardC Type (Outdoor Unit)U1 U2 1 2 G L1 L2U2U1L1L2U1U212G21WHTRemotecontrolle

Page 33 - Not good

39WARNINGLoose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist.Therefore, ensure that all wiring

Page 34

4 R407C tools Item compatible Remarks with R410A? Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, a

Page 35

405. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLERIMPORTANTWhen using this air conditioner with the wireless remote controller it may sometimes be imp

Page 36

415-2. Room Temperature Sensor SettingThe room temperature sensors are built into the indoor unit and the wireless remote controller. Either of these

Page 37 - 4. ELECTRICAL WIRING

42<CZ-RWSU1U>4-Way Cassette Type (U1 Type)5-5. Indicator Section Installation Remove the ceiling panel and indicator cover and install the ind

Page 38 - C Type (Outdoor Unit)

43Ceiling Type (T1 Type)5-7. Indicator Section InstallationRemove the side panel to install the indicator section.(Fig. 5-8)(1) Remove the side panel.

Page 39 - Stranded wire

445-9. Electrical Wiring5-10-1. How to use the test run setting (U1, T1 Types)(1) Set DIP switch [DS] No. 1 on the wireless receiverunit PCB from OFF

Page 40

455-11. Misoperation Alarm IndicatorsAlarm indicator lamps on the indoor unit indicate the error cause if the air conditioner fails to operate upon be

Page 41 - Operation

46<CZ-RWSC1U>CAUTION If the signal receiving unit is installed near a rapid-start or inverter type fluorescent lamp (neither one uses glow lam

Page 42 - Operating

47 When using the signal receiving unit on a wall withthe front exposed, choose a wall surface that thesignal receiving unit can be mounted on.(1) In

Page 43 - Electrical component box

485-13. Electrical WiringCAUTIONBe sure to do the wiringcorrectly (incorrectwiring will damage theequipment). Recommended wire diameter and allowable

Page 44 - All OFF( ) for

495-15. Misoperation Alarm IndicatorsA blinking lamp for other than the signal receiving unitfi lter shows that a problem has occurred in the unit, som

Page 45 - (STANDBY

53-2. Use R410A exclusive cylinder only. When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case,

Page 46

505-16. Basic Wiring DiagramCAUTIONBe sure to do the wiringcorrectly (incorrect wiringwill damage the equipment). Wiring procedureCarry out the wiring

Page 47 - Wood screws (2)

515-17. Wiring System Diagram for Group ControlThis diagram shows when several units (maximum of8) are controlled by a signal receiving unit (mainunit

Page 48 - TEST RUN

525-18. Wiring System Diagram for Multiple Remote Controllers To operate 1 indoor unit with 2 signal receiving unitsset at different locations.CAUTIO

Page 49

53<CZ-RWSK1U>5-19. Test Run Procedure Wall mounted Type (K1 Type)5-20. Check Items Before the Test Run(1) Turn ON the remote power switch a

Page 50 - Indoor unit

545-21. Preparing for the Test Run5-21-1. Changing the room temperature sensor Room temperature sensors are installed inside the indoor unit and the

Page 51 - Connection wiring

555-22. Precautions Request that the customer be present at the time the test run is performed. Explain the Operating Instructions tothe customer, an

Page 52

565-23. When Setting Indoor Unit Control PCB Switch for Wall Mounted Indoor UnitWhen using both the wired and wireless remote controller, refer to the

Page 53 - SENSOR button

575-24. Diagnosis TableWired remote CauseE 0 1E 0 2E 0 9E 1 4E 0 4E 0 6E 1 5E 1 6E 2 0P 0 5L 0 2P 0 9 displayedL 0 7 displayedIndoor unit ٨٨٨٨٨٨٨٨٨٨

Page 54 - Indicator

586. APPENDIXName of Parts Water drainCeiling panel(optional)Air outlet(4 locations)Air intake grille(air intake)4-Way Cassette type (U1 type)Water d

Page 55

59CAUTION1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic parts using very hot water.2. Some metal edges

Page 56

6Page CONTENTSPage IMPORTANT! ... 2Please Read Before StartingCheck of Density LimitPreca

Page 57 - 5-24. Diagnosis Table

60U1 typeAir intake grilleLatchSafety chainBolt screwsAir filterCare and Cleaning (continued) 1. Use a screwdriver to remove the bolt screw on each si

Page 58 - 6. APPENDIX

61Air intake grillfinger-holdAir filterAir intake grillAir filter finger-holdLatchAir filter finger-hold* Take hold of the finger-hold on the air filt

Page 59

62CAUTION1. Certain metal edges and the condenser fins are sharp and may cause injury if handled improperly; special care should be taken when you cl

Page 60

63TroubleshootingIf your air conditioner does not work properly, first check the following points before requesting service. If it still does not work

Page 61

DC0811-21111Printed in JapanPanasonic_PAC-i_IndoorUnit_US-le1 1Panasonic_PAC-i_IndoorUnit_US-le1 1 2011/11/02 15:17:412011/11/02 15:17:41

Page 62

71. GENERALThis booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the

Page 63

8Full-scale installation diagram Flare insulator Washer Insulating tape Hose band Packing Drain insulator Drain hose Drain hose adaptor Sealing putty

Page 64 - Printed in Japan

9Part Name Figure Q’ty Part Name Figure Q’ty Drain hose Wire jointWood screwWired remote controller (comes with 7-7/8 in. wire) 2 1 1 2 1 1 1 1 1