22
11. Installation Instruction
11.1 Select the Best Location
11.1.1 Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchens, workshops and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 8.2 ft.
11.1.2 Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Recommended installation height for outdoor unit
should be above the seasonal snow level.
Example: For E18NKUA
If the unit is installed at 41 ft distance, the quantity
of additional refrigerant should be 2.46 oz ....
(41 - 32.8) ft x 0.3 oz/ft = 2.46 oz.
11.2 Indoor/Outdoor Unit
Installation Diagram
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - 11. Installation Instruction

22 11. Installation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit  Do not install the unit in excessive oil fume area such as kitche

Page 2 - 11.3 Indoor Unit

23 11.3 Indoor Unit 11.3.1 How to Fix Installation Plate The mounting wall must be strong and solid enough to prevent it from the vibration. The c

Page 3

24 11.3.3 Indoor Unit Installation 11.3.4 For the right rear piping 11.3.5 For the right bottom piping 11.3.6 For the embedded piping

Page 4

25 11.3.7 Connect the Cable to the Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2.

Page 5

26 11.3.8 Wiring Stripping and connecting requirement 11.3.9 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the b

Page 6 - 11.4 Outdoor Unit

27 11.4 Outdoor Unit 11.4.1 Install the Outdoor Unit  After selecting the best location, start installation according to indoor/outdoor unit instal

Page 7

28 11.4.3 Evacuation of the equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the followi

Page 8 - 11.4.5 Piping Insulation

29 9. Secure the wire onto the control board with the holder (clamper). 10. After completing wiring connections, reattach the particular plate con

Commentaires sur ces manuels

Pas de commentaire