Split System Submittal Data
USPA-AC-BAC-128
Requires (1) Communication Adaptor (CZ-CFUNC1U)
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Mechanical and Electrical Specifications
Power 9 to 30Vdc +/- 10%, Max.:125mA.
24Vac +/- 10% 50-60Hz,
Max.:127mA.
Enclosure Plastic, type PC (UL 94 V-0).
4.5" X 4.5" X 2.5"
Mounting Wall
DIN rail EN60715 TH35
BACnet/IP Port 1 x Ethernet Port 10Base-t
(RJ45).
LED Indicators 1 x Power.
2 x Ethernet port link and activity
(LNK, ACT).
Configuration Via console port (EIA232) or
Ethernet Port.
Operational Temperature 32°F to 158°F
Operational Humidity 5 to 95 %, non condensing.
BACnet Interface
Device Type Server Server
BACnet Type BACnet/IP (accessible through
Ethernet).
BACnet Configurable
Parameters
IP Address.
Subnet Mask.
Default Gateway Address.
Device Name.
Device Instance Number.
Interactivity with BACnet Internal point’s Read/Write
allowed.
Subscription requests (COV)
allowed.
Features
Global and Individual Operation/
Setting Objects
Global and Individual Monitor/
Status Objects
• All On/Off • On/Off
• On/Off • Mode
• Mode • Setpoint
• Setpoint • Fan Speed
• Fan Speed • Air Direction
Air Direction (N/A for Ducted
Units)
• Space Temperature
• Filter Sign Reset Prohibited Thermostats
Functions
• Prohibit Thermostat Functions • Filter Status
• Occupancy/Unoccupied All • Unit and System Error Codes
Occupied/Unoccupied Cool
Setpoints
• CZ-FUNC1U Error Codes
Occupied/Unoccupied Heat
Setpoints
• Occupied/Unoccupied Mode
• Consumption Reset Today, Yesterday and Total
Consumption.
Product Overview
The USPA-AC-BAC-128 is a
BACnet over IP server device,
capable of monitoring and
controlling ECOi, ECOiEX and
PACi systems. Up to 128 indoor
units and 30 outdoor units can be
integrated.
Includes an Auto-Discover
feature that detects connected
Panasonic equipment for a quick
and easy setup and Integration.
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Split System Submittal Data

Split System Submittal DataUSPA-AC-BAC-128 Requires (1) Communication Adaptor (CZ-CFUNC1U)Approval:Date:Construction:Unit#:Drawing#:Job Name:Locatio

Page 2 - System Example

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144http://www.panasonic.com/airconDimensions Minimum C

Commentaires sur ces manuels

Pas de commentaire